A Procedure For Performance Experimental Analysis Of A Globe Control Valve

dc.contributor.authorHoursan, Hesam
dc.contributor.authorMoradi, Mohamad
dc.contributor.authorHadjiazim, Mohammad Omid
dc.contributor.authorAhmadian, Mohammad Taghi
dc.contributor.authorBarari, Ahmad
dc.date.accessioned2018-11-09T19:21:04Z
dc.date.available2018-11-09T19:21:04Z
dc.date.issuedMay-18
dc.description.abstractControl valves are known as the final control element in hydraulic closed/open loops of modern process industries around the world. Proper selection of control valve leads to enhanced performance curve of the hydraulic systems and therefore increases the efficiency, reliability, profitability and safety of the system. Flow coefficient (CV) of a control valve describes the relation between the pressure drop across the valve and the flow passing through it. Despite many computational efforts for calculating the exact value and curve of CV, the experimental procedure of the CV test has not been documented well. We used a control valve test-set up designed based on the standards ANSI/ISA-75.02-1996 and IEC 60534-2-3 (2013) to evaluate the performance of a 3 in. control valve. Upon extracting the results in terms of inlet, and outlet pressure and flow, the characteristic parameters such as CV and opening percentage were derived and compared with an ideal curve. Error analysis was performed to account for the tolerance of the measured parameters by the measuring devices. The results show acceptable agreement within the criteria of a reference standard approving the validity of the design method.en_US
dc.identifierCSME056
dc.identifier.isbn978-1-77355-023-7
dc.identifier.urihttp://hdl.handle.net/10315/35410
dc.identifier.urihttp://dx.doi.org/10.25071/10315/35410
dc.language.isoenen_US
dc.publisherCSME-SCGMen_US
dc.rightsThe copyright for the paper content remains with the author.
dc.subjectCodes and standardsen_US
dc.subjectEngineering Analysis & Designen_US
dc.subjectFluid Mechanicsen_US
dc.subjectControl valveen_US
dc.subjectFlow coefficienten_US
dc.subjectIdeal curveen_US
dc.subjectTest set-upen_US
dc.subjectPerformanceen_US
dc.titleA Procedure For Performance Experimental Analysis Of A Globe Control Valveen_US
dc.typeArticleen_US

Files

Original bundle
Now showing 1 - 1 of 1
Loading...
Thumbnail Image
Name:
CSME2018_paper_56.pdf
Size:
873.66 KB
Format:
Adobe Portable Document Format
Description:
License bundle
Now showing 1 - 1 of 1
No Thumbnail Available
Name:
license.txt
Size:
1.83 KB
Format:
Item-specific license agreed upon to submission
Description: