Fault Analysis and Control of DFIGs for Grid Code Compliance and Protection of Power System

dc.contributor.advisorHooshyar, Ali
dc.contributor.authorMohammadpour, Hassan
dc.date.accessioned2023-12-08T14:22:09Z
dc.date.available2023-12-08T14:22:09Z
dc.date.issued2023-12-08
dc.date.updated2023-12-08T14:22:08Z
dc.degree.disciplineComputer Science
dc.degree.levelDoctoral
dc.degree.namePhD - Doctor of Philosophy
dc.description.abstractInverter-based resources (IBRs) are growing at exponential rates in today's power systems. Therefore, a sizable portion of the measurements of relays is expected to come from IBRs. However, the fault current characteristics of IBRs put the operation of the relays in jeopardy as they are different than that of synchronous generators' (SGs) based on which the relays' operating principles are developed. Therefore, different countries have progressively revised their grid codes (GCs) to reduce the likelihood of protection malfunctions and ensure stable and continuous operation of power systems. Similar to emerging regional GCs, the recently approved IEEE 2800 Standard mandates that IBRs generate negative-sequence current during low-voltage ride-through (LVRT) conditions. The 2800 Standard requires that the IBRs' negative-sequence current lead the negative-sequence voltage by 90-100 degrees to emulate SGs and reduce the likelihood of protection malfunction. However, the limitations of existing doubly-fed induction generators (DFIGs) led the Standard to exempt the DFIGs from this requirement and allow a wider range for their negative-sequence current angle. Meanwhile, the 2800 Standard also acknowledged that this exemption had unidentified and potentially negative impacts on protective relays. This dissertation, for the first time, (i) sheds light on several so-far-unknown DFIG characteristics that impact the angle of the negative-sequence current during LVRT, (ii) reveals the impacts of the above DFIG exemption on industrial relays, and (iii) develops a solution to prevent the need for this exemption in the future revisions of the IEEE 2800 Standard. This dissertation also investigates the challenges brought about by the DFIGs during the crowbar connection and rectification mode of operation, i.e., interrupted control of the DFIG's converters, now affecting the performance of distance relays that are installed at a DFIG-based wind farm substation. The focus is on the relays implemented using the apparent impedance approach and the commercially developed reactance method. It is revealed that the phase elements of a distance relay that uses these methods are prone to under-/over-reach in the systems with DFIGs. The exclusive fault behavior of DFIGs along with different units of a distance relay is scrutinized to identify the root causes. To address the relay problems, a communication-assisted method with minimal bandwidth requirement is developed, which provides non-delayed fast tripping over the entire length of the line.
dc.identifier.urihttps://hdl.handle.net/10315/41597
dc.languageen
dc.rightsAuthor owns copyright, except where explicitly noted. Please contact the author directly with licensing requests.
dc.subjectElectrical engineering
dc.subjectEnergy
dc.subject.keywordsDoubly-fed induction generator
dc.subject.keywordsDFIG
dc.subject.keywordsGrid code
dc.subject.keywordsIEEE 2800 Standard
dc.subject.keywordsLow-voltage ride-through
dc.subject.keywordsLVRT
dc.subject.keywordsFault ride-through
dc.subject.keywordsFRT
dc.subject.keywordsInverter-based resources
dc.subject.keywordsIBR
dc.subject.keywordsWind turbine
dc.subject.keywordsInduction machine
dc.subject.keywordsRotor side converter
dc.subject.keywordsRSC
dc.subject.keywordsGrid side converter
dc.subject.keywordsGSC
dc.subject.keywordsCrowbar
dc.subject.keywordsChopper
dc.subject.keywordsOff-nominal frequency
dc.subject.keywordsPhasor measurement
dc.subject.keywordsProtection
dc.subject.keywordsDistance relay
dc.subject.keywordsPermissive overreach transfer trip
dc.subject.keywordsPOTT
dc.subject.keywordsPhase selection
dc.subject.keywordsDistance element
dc.subject.keywordsFault current
dc.subject.keywordsDFIG control
dc.titleFault Analysis and Control of DFIGs for Grid Code Compliance and Protection of Power System
dc.typeElectronic Thesis or Dissertation

Files

Original bundle
Now showing 1 - 1 of 1
Loading...
Thumbnail Image
Name:
Mohammadpour_Hassan_2022_PhD.pdf
Size:
5.46 MB
Format:
Adobe Portable Document Format
License bundle
Now showing 1 - 2 of 2
No Thumbnail Available
Name:
license.txt
Size:
1.87 KB
Format:
Plain Text
Description:
No Thumbnail Available
Name:
YorkU_ETDlicense.txt
Size:
3.39 KB
Format:
Plain Text
Description:

Collections