An Experimental Evaluation On Air Conditioning Performance With Vairtex Air Director Applied On Residential Condenser Unit

Loading...
Thumbnail Image

Date

May-18

Authors

Nguyen, Vien
Matida, Edgar
Godbout, Gerard

Journal Title

Journal ISSN

Volume Title

Publisher

CSME-SCGM

Abstract

Thermodynamic performance measurements of a 1.5 ton residential air conditioning system and fluid flow hot-wire velocity measurements at the outlet of the condenser were performed with and without an add-on device (VairTEX Air Director added on top of the condenser unit). The Air Director modified all three velocity components at the condenser exit. Data from hot-wire confirmed the Air Director reduced the radial component while enhancing swirling factor and adding 48.7% volumetric flow rate across the condenser unit. By streamlining the flow, the Air Director led to an improvement of 5% in terms of overall coefficient of performance of the air conditioning unit and 4.5% reduction in compressor power consumption.

Description

Paper presented at 2018 Canadian Society of Mechanical Engineers International Congress, 27-30 May 2018.

Keywords

Environmental Engineering, Air Conditioning, Condenser, Coefficient Of Performance, Hot-Wire, Compressor Power, Air Director

Citation